Detailed description:
• Small size and light weight. • High reliability and low price. • The circuit has a wide input voltage range. • High conversion efficiency and low operating temperature rise. • Built-in filter circuit, less external radiation interference. • It has basic protection circuit and good adaptability to the environment. • 4 hours, 100% full load aging and full range of functional tests. | ||
model characteristic | SAMM-150-1B | |
Rated output voltage | DC +24V | BAT +27.6V |
Output interface location | The eight-digit P=9.5mm covered terminal block is marked AC-L, AC-N, DC+, DC-; BAT-, BAT+, BATSW | |
Output voltage range | Setting error: ±0.5V | Setting error: ±0.6V; |
Rated output current | 6A | 0.5A |
Load current range | 0.5~6A ( MAX=10A ) | 0.2~0.5A ( MAX=0.5A ) |
Output voltage ripple | Vp-pmax<180 mV | Vp-pmax<200 mV |
Li ; Lo Adjustment rate | Line:±0.5%;Load:±0.5% | Line:±1%;Load:±15%(BAT±3%) |
Comprehensive voltage stabilization accuracy | ±1% | ±16%(BAT±4%) |
Rated output power | 150W | |
Rated working efficiency | ≥80% (output power is rated value) | |
Rated input voltage | Operating voltage: AC176V-264V Rated voltage: AC220V Interface location: Three-position covered socket marked AC-L, AC-N, FG | |
Rated input current | Rated current: AC0.5A, current range AC0.5~1A | |
AC input frequency | Rated AC voltage frequency range 47~63Hz, sine wave | |
Input surge current | The impact current on the power supply grid at the moment of power-on: the maximum value during cold start is 60A/10mS. | |
Output overload protection | The +12V overload protection point is about 105%~120% of the rated output power; the overload protection is an online current limiting and voltage reduction method; the short circuit protection needs to reset the input | |
UPS battery management function | An external battery (capacity 5~30AH) is required for backup power supply. When the AC power supply is stopped, the system automatically switches to the backup power supply. The system conversion is ≤50mS. When the AC power supply is normal, it automatically switches to the AC power supply and battery management (to enable the UPS function, you need to connect BAT+ with BAT.SW phase short circuit) | |
It has the function of floating charging for external batteries (5~30AH). The battery has an undervoltage of 10V±0.6V when discharging the load, and the short circuit protection function can automatically reset. | ||
Power time parameters | Preparation time (SETUP TIME) ≈ 200mS; Stability time (RISE TIME) ≈ 50mS; Holding time (HOLD UP TIME) ≈ 20mS | |
Electrical strength parameters | Input-output: >AC1.5KV; Input-casing: >AC1.5KV; Output-casing: >AC0.5KV Leakage current <5mA 50Hz 1min. | |
Operating temperature parameters | The working temperature drift coefficient is about ±0.03[%/℃]; the absolute temperature rise coefficient is about 0.50[℃/W]; when the working output is rated power, the absolute temperature rise of the body is 25℃±5℃ | |
Environmental condition parameters | Storage environment: -20℃~+85℃; 10%~95%RH. Working environment: -10℃~+50℃; 20%~90%RH. (Varies depending on usage environment and power) | |
Working heat dissipation method | Designed to work continuously, with self-cooling to assist heat dissipation. (Differences in usage environment and installation location affect power usage and lifespan) | |
Appearance installation dimensions | Specifications and dimensions: L195×W110×H50mm3; Installation dimensions: L188×W98mm2, L188×W23mm2 | |
Net weight and appearance | The total weight is about 850g; the bottom shell is made of 1.5mm thick aluminum with a silver sand-oxygen surface treatment; the cover shell is 0.8mm thick iron with a silver electroplastic surface treatment. | |
Certified safety specifications | National standard GB-4943 | |
Note: 1) The above detection indicators are measured under the following conditions: within the input rated voltage and output rated load range, the environment is 25℃, 85%RH. , when there is no wind around 2) Output DC voltage ripple detection: Use a parallel twisted wire with a length of 30cm and a cross-section of 1mm2 connected to one end of a 0.1μF and 0.47μF capacitor to bypass the detection point and detect 100Hz respectively. The maximum peak-to-peak value of the main frequency ripple is Vp-p100Hz and the maximum peak-to-peak value of the comprehensive ripple is Vp-pmax. 3) Li voltage regulation rate: when the load is at the rated value, the input voltage changes within the rated range; Lo load regulation rate: when the input is at the rated voltage value, the load changes from zero to the rated value.
|