Detailed description:
• Small size and light weight. • High reliability and low price. • The circuit has a wide input voltage range. • High conversion efficiency and low operating temperature rise. • Built-in filter circuit, less external radiation interference. • It has basic protection circuit and good adaptability to the environment. • 4 hours, 100% full load aging and full range of functional tests. | ||
model characteristic | SAOG-250-1B | |
Rated output voltage | DC +24V | BAT +27.6V |
Output interface location | The four terminal blocks are marked DC+, DC-, BAT-, BAT+, BAT.SW respectively. | |
Output voltage range | Setting error: ±0.2V; Adjustable range: ±10% | Setting error: ±0.5V; |
Rated output current | 10A | 1A |
Load current range | 0~10A ( MAX=10A ) | 0~1A ( MAX=1A ) |
Output voltage ripple | Vnor<9mV ;Vp-p100Hz<200mV;Vp-pmax<200 mV | Vnor<12mV ;Vp-p100Hz<220mV;Vp-pmax<250 mV |
Li ; Lo Adjustment rate | Line:±0.5%;Load:±0.8% | Line:±1%;Load:±15 % |
Comprehensive voltage stabilization accuracy | ±1% | ±20% |
Rated output power | 250W | |
Rated working efficiency | ≥75% (output power is rated value) | |
Rated input voltage | Rated voltage: AC176~265V, operating voltage: AC220V±15%. Interface location: Three-position uncovered socket marked AC-L, AC-N, FG | |
Rated input current | Rated current: AC3.0A, current range AC1.0~4.0A | |
AC input frequency | Rated AC voltage frequency range 47~63Hz, sine wave | |
Input surge current | The impact current on the power supply grid at the moment of power-on: the maximum value during cold start is 60A/10mS. | |
Input voltage protection | The input allowable range is AC0~280V; the overvoltage protection point is AC300V±5V, and the power supply enters a non-restorable shutdown state. | |
Output overload protection | The +24V overload protection point is about 105%~120% of the rated output power; the overload protection is an online current limiting and voltage reduction method; the short circuit protection needs to reset the input | |
UPS battery management function | An external 24V lead-acid battery (capacity 5~30AH) is required for backup power supply. When the AC power supply is stopped, the system automatically switches to the backup power supply. The system switches without time interruption. When the AC power supply is normal, it automatically switches to the AC power supply and manages the battery. | |
It has the function of floating charging for external batteries (5~30AH), and each protection function can be automatically reset. | ||
Power time parameters | Preparation time (SETUP TIME) ≈ 200mS; Stability time (RISE TIME) ≈ 50mS; Holding time (HOLD UP TIME) ≈ 20mS | |
Electrical strength parameters | Input terminal-output terminal: AC1.5KV; input terminal-casing: AC1.5KV; output terminal-casing: AC0.5KV Leakage current 5mA 50Hz 1min. | |
Operating temperature parameters | The working temperature drift coefficient is about ±0.03[%/℃]; the absolute temperature rise coefficient is about 0.50[℃/W]; when the working output is rated power, the absolute temperature rise of the body is 35℃±5℃ | |
Environmental condition parameters | Storage environment: -20℃~+85℃; 10%~95%RH. Working environment: 0℃~+45℃; 20%~90%RH. (Varies depending on usage environment and power) | |
Working heat dissipation method | Designed for continuous working mode, air cooling (differences in usage environment and installation location affect power usage and lifespan) | |
Appearance installation dimensions | Specifications and dimensions: L225×W118×H69mm3; | |
Net weight and appearance | The total weight is about 1.0kg; the shell is 1.0mm thick iron shell with white surface; | |
Certified safety specifications | National standard GB-4943 | |
Note: 1) The above detection indicators are measured under the following conditions: within the input rated voltage and output rated load range, the environment is 25℃, 85%RH. , when there is no wind around 2) Output DC voltage ripple detection: Use a parallel twisted wire with a length of 30cm and a cross-section of 1mm2 connected to one end of a 0.1μF and 0.47μF capacitor to bypass the detection point and detect 100Hz respectively. The maximum peak-to-peak value of the main frequency ripple is Vp-p100Hz and the maximum peak-to-peak value of the comprehensive ripple is Vp-pmax. 3) Li voltage regulation rate: when the load is at the rated value, the input voltage changes within the rated range; Lo load regulation rate: when the input is at the rated voltage value, the load changes from zero to the rated value. |